Untitled document

Case
No judgment structure available for this case.

Electricity Safety (Bushfire Mitigation) Amendment Regulations 2016

S.R. No. 32/2016

TABLE OF PROVISIONS

Regulation  Page

1Objective

2Authorising provisions

3Commencement

4Principal Regulations

5Definitions

6Prescribed particulars for bushfire mitigation plans—major electricity companies

7Prescribed information about bushfire mitigation plans to be made publicly available by major electricity companies

8Prescribed form of notice to be given before inspection

9Schedule

10New Schedule 2 inserted

═══════════════

Endnotes

STATUTORY RULES 2016

S.R. No. 32/2016

Electricity Safety Act 1998

Electricity Safety (Bushfire Mitigation) Amendment Regulations 2016

The Governor in Council makes the following Regulations:

Dated: 26 April 2016

Responsible Minister:

LILY D'AMBROSIO
Minister for Energy and Resources

ANDREW ROBINSON

Clerk of the Executive Council

1Objective

The objective of these Regulations is to amend the Electricity Safety (Bushfire Mitigation) Regulations 2013 to make provision for requirements for major electricity companies to increase safety standards on specific components of their networks in order to reduce bushfire risk.

2Authorising provisions

These Regulations are made under sections 151, 151A and 157 of the Electricity Safety Act 1998.

3Commencement

These Regulations come into operation on 1 May 2016.

4Principal Regulations

In these Regulations, the Electricity Safety (Bushfire Mitigation) Regulations 2013[1] are called the Principal Regulations.

5Definitions

In regulation 5 of the Principal Regulations insert

"Automatic Circuit Recloser means a device in relation to a SWER line that—

(a)may be remotely controlled; and

(b)is able automatically to interrupt and reclose an electric circuit by means of a programmed sequence that involves—

(i)opening and reclosing the electric circuit; and

(ii)resetting the electric circuit; and

(iii)holding the electric circuit closed; and

(iv)permanent interruption of the electric circuit;

Central Plan Office means the Central Plan Office of the Department of Environment, Land, Water and Planning;

electric line construction area means land delineated and shown bounded by an orange line on plans lodged in the Central Plan Office and numbered LEGL./16-199 to LEGL./16-231;

high impedance faults means a resistance value in ohms that is equal to twice the nominal phase-to-ground network voltage in volts;

I2t means a measure of the thermal energy associated with the current flow, where I is the current flow in amps and t is the duration of current flow in seconds;

low impedance faults means a resistance value in ohms that is equal to the nominal phase‑to-ground network voltage in volts divided by 31·75;

polyphase electric line means an electric line comprised of more than one phase of electricity with a nominal voltage between 1 kV and 22 kV;

required capacity means, in the event of a phase‑to-ground fault on a polyphase electric line, the ability—

(a)to reduce the voltage on the faulted conductor in relation to the station earth when measured at the corresponding zone substation for high impedance faults to 250 volts within 2 seconds; and

(b)to reduce the voltage on the faulted conductor in relation to the station earth when measured at the corresponding zone substation for low impedance faults to—

(i)1900 volts within 85 milliseconds; and

(ii)750 volts within 500 milliseconds; and

(iii)250 volts within 2 seconds; and

(c)during diagnostic tests for high impedance faults, to limit—

(i)fault current to 0·5 amps or less; and

(ii)the thermal energy on the electric line to a maximum I2t value of 0·10;

SWER line means a single wire earth return electric line;

wholly or substantially replaced means the planned replacement or relocation of an electric line that involves—

(a)the relocation of at least 4 consecutive spans of the electric line; or

(b)the replacement of conductors on at least 4 consecutive spans of the electric line.".

6Prescribed particulars for bushfire mitigation plans—major electricity companies

(1)After regulation 7(1)(h) of the Principal Regulations insert

"(ha)details of the preventative strategies and programs referred to in paragraph (h) (including details in relation to timing and location) by which the major electricity company will ensure that—

(i)in its supply network, each polyphase electric line originating from a selected zone substation has the required capacity; and

(ii)on and from 1 May 2023, in its supply network, each polyphase electric line originating from every zone substation specified in Schedule 2 has the required capacity;

(hb)details of testing that will be undertaken before the specified bushfire risk period each year by which the major electricity company will ensure that its supply network can operate to meet the required capacity in relation to each polyphase electric line in accordance with paragraph (ha);

(hc)details of the preventative strategies and programs referred to in paragraph (h) (including details in relation to timing and location) by which the major electricity company will ensure that, on and from 1 May 2016, within an electric line construction area, each electric line with a nominal voltage of between 1 kV and 22 kV that is constructed, or is wholly or substantially replaced, in its supply network is a covered or underground electric line;

(hd)details of the processes and procedures by which the major electricity company will ensure that, before 1 May 2023, the major electricity company has installed an Automatic Circuit Recloser in relation to each SWER line in its supply network;".

(2)In regulation 7(1)(n)(vi) of the Principal Regulations, after "plan;" insert "and".

(3)After regulation 7(1)(n)(vi) of the Principal Regulations insert

"(vii)before the specified bushfire risk period each year, report to Energy Safe Victoria the results of testing undertaken in that year in accordance with regulation 7(1)(hb);".

(4)After regulation 7(2) of the Principal Regulations insert

"(3)For the purposes of subregulation (1)(ha)(i)—

(a)the major electricity company must select a sufficient number of zone substations so that—

(i)at 1 May 2019, the points set out in column 6 of the Table in Schedule 2 in relation to each zone substation selected, when totalled, are not less than 30; and

(ii)at 1 May 2021, the points set out in column 6 of the Table in Schedule 2 in relation to each zone substation selected, when totalled, are not less than 55; or

(b)if there are an insufficient number of zone substations (specified in Schedule 2) in a major electricity company's supply network for the major electricity company to comply with paragraph (a)(i) or (ii), the major electricity company must ensure that each polyphase electric line originating from every zone substation that is specified in Schedule 2 and is in its supply network has the required capacity.".

7Prescribed information about bushfire mitigation plans to be made publicly available by major electricity companies

After regulation 7A(f) of the Principal Regulations insert

"(fa)the company's plan for testing to ensure that its supply network can operate to meet the required capacity in relation to each polyphase electric line originating from a zone substation specified in Schedule 2;

(fb)the details of the processes and procedures for installing an Automatic Circuit Recloser in relation to each SWER line in its supply network;".

8Prescribed form of notice to be given before inspection

In regulation 12 of the Principal Regulations, for "the Schedule" substitute "Schedule 1".

9Schedule

In the Schedule to the Principal Regulations—

(a)for the heading "SCHEDULE" substitute


"Schedule 1—Notice of inspection";

(b)omit the heading "NOTICE OF INSPECTION".

10New Schedule 2 inserted

After Schedule 1 to the Principal Regulations insert

"Schedule 2—Zone substations

Regulations 7(1)(ha) and (3) and 7A(fa)

Column 1 Column 2 Column 3 Column 4 Column 5 Column 6
Item Name Code Latitude Longitude Points
1 Winchelsea   WIN   -38·23644 144·00102 5
2 Colac   CLC   -38·34092 143·60619 5
3 Eaglehawk   EHK   -36·71772 144·25089 5
4 Woori Yallock   WYK   -37·77634 145·52933 5

5

Maryborough  

MRO  

-37·04909

143·73727

5

6

Seymour  

SMR  

-37·02548

145·14068

5

7

Ballarat South  

BAS  

-37·59450

143·79908

5

8

Bendigo TS  

BET  

-36·78289

144·25296

5

9

Wangaratta  

WN  

-36·35744

146·31022

5

10

Castlemaine  

CMN  

-37·07182

144·20637

4

11

Camperdown  

CDN  

-38·22599

143·15655

4

12

Woodend  

WND  

-37·33385

144·51729

4

13

Kinglake  

KLK  

-37·51440

145·31615

4

14

Rubicon A  

ALA, MVE

-37·29287

145·81850

4

15

Bairnsdale  

BDL  

-37·82537

147·61261

4

16

Geelong  

GL  

-38·13477

144·33741

4

17

Ballarat  

BAN  

-37·50088

143·85096

4

18

Waurn Ponds  

WPD  

-38·21082

144·30380

4

19 Lilydale   LDL   -37·76339 145·35840 3

20

Wodonga and Tallangatta  

WOTS  

-36·15439

146·94682

3

21

Myrtleford  

MYT                   

-36·55745

146·72525

3

22

Barnawartha  

BWA  

-36·10556

146·67345

3

23

Kilmore South  

KMS  

-37·31798

144·97174

3

24

Kalkallo  

KLO  

-37·53833

144·94140

3

25

Gisborne  

GSB  

-37·45352

144·57625

3

26

Belgrave  

BGE  

-37·93056

145·36096

3

27

Moe  

MOE  

-38·18424

146·25908

3

28

Mansfield  

MSD  

-37·05458

146·08802

2

29

Ferntree Gully  

FGY  

-37·89304

145·29167

2

30

Eltham  

ELM  

-37·71675

145·13881

2

31

Ringwood North  

RWN  

-37·79260

145·23449

2

32

Charlton  

CTN  

-36·26562

143·35478

2

33

Benalla  

BN  

-36·55160

145·98000

2

34

Koroit  

KRT  

-38·31541

142·43245

2

35

Hamilton  

HTN  

-37·73876

142·02283

2

36

Terang  

TRG  

-38·23860

142·91531

2

37

Merbein  

MBN  

-34·16805

142·05807

1

38

Stawell  

STL  

-37·05833

142·77839

1

39

Bendigo  

BGO  

-36·76102

144·27897

1

40

Ararat  

ART  

-37·28308

142·93030

1

41

Coolaroo  

COO  

-37·64207

144·93391

1

42 Corio   CRO   -38·07445 144·35898 1

43

Lang Lang  

LLG  

-38·26605

145·56266

1

44

Wonthaggi  

WGI  

-38·60885

145·58860

1

45

Sale  

SLE  

-38·10364

147·06972

1

".

═══════════════

Endnotes


[1] Reg. 4: S.R. No. 62/2013 as amended by S.R. Nos 67/2015 and 68/2015.

Actions
Download as PDF Download as Word Document

Citations
Untitled document

Cases Citing This Decision

0

Cases Cited

0

Statutory Material Cited

0