Telegraph Lines Protection Regulations 1920 (Cth)
STATUTORY RULES.
REGULATIONS UNDER THE POST AND TELEGRAPH ACT 1901-1916.
I,
THE GOVERNOR-GENERAL in and over the Commonwealth of Australia, acting with the
advice of the Federal Executive Council, hereby make the following Regulations
under the
Dated this first day of December, 1920.
FORSTER,
Governor-General.
By His Excellency’s Command,
GEO. H. WISE,
Postmaster-General.
REGULATIONS FOR SECURING THE TELEGRAPH LINES OF THE POSTMASTER-GENERAL FROM INTERFERENCE OR INJURIOUS AFFECTION BY ELECTRIC LINES OR WORKS.
Part I.—General.
Part I.—General.
Part II.—Electric Tramways.
Part III.—Electric Light and Power Works and Lines.
Part IV.—Miscellaneous.
“Aerial line” means an electric line which is placed above ground and in the open air.
“Current” means an electric current.
“Difference of potential” means difference of electrical potential.
“Efficiently connected with earth” means connected with the general mass of the earth in such a manner as to insure at all times an immediate and safe discharge of energy.
“Energy” means electrical energy.
“Generator” means a dynamo or other apparatus used for the generation of energy.
“High pressure” means a pressure exceeding 6,600 volts (alternating or continuous) between any conductor and the earth.
“Intermediate pressure” means a pressure exceeding 650 volts, but not exceeding 6,600 volts (alternating or continuous) between any conductor and the earth.
“Low pressure” means a pressure not exceeding 650 volts (alternating or continuous) between any conductor and the earth.
“Pressure” means the difference of potential between any two conductors through which a supply of energy can be given, or between any part of a conductor and the earth.
“The Act” means the
Post and Telegraph Act 1901-1916.
Part II.—Electric Tramways.
(2) The regulations in Part III. shall, so far as applicable, apply to all lines used for the transmission of energy from the generator to transformer sub-stations by means of alternating currents, and the insulation resistance of those lines shall not be permitted to fall below the equivalent of 10 megohms for a length of 1 mile.
(3) A test of the insulation resistance of all such lines shall be made at least once in each month.
(
a )the uninsulated return shall be connected with the negative terminal of the generator, and the negative terminal of the generator shall be directly connected through a current indicator with earth; or(
b )the uninsulated return shall be connected with the negative terminal of the generator by one or more insulated return conductors, of which the ends connected with the uninsulated return shall be connected through a current indicator with earth; and the generator shall have no other connexion with earth,
(2) If, in the last mentioned case, the current indicator cannot conveniently be placed at the connexion of the uninsulated return with the insulated return, the instrument may consist of a current indicator at the generating station connected by insulated wires to the terminals of a resistance interposed between the returns and the earth connexion or connexions the resistance shall be such that the maximum current permitted by those Regulations to pass from the earth connexions to the generator shall produce a difference of potential not exceeding 1 volt between the terminals. The indicator shall be so constructed as to indicate correctly the current passing through the resistance when connected to the terminals by the insulated wires mentioned in this regulation.
(3) The earth connexions required by this regulation shall be either two separate earth connexious, or connexions with a main for water supply of not less than 3 inches internal diameter.
(4) The two earth connexions shall be placed not less than 20 yards apart, and shall be constructed, laid, and maintained so as to secure electrical contact with the general mass of earth, and so that an electro-motive force not exceeding 4 volts shall suffice to produce a current of at least 2 amperes from one earth connexion to the other through the earth, and a test shall be made at least once in every month to ascertain whether this requirement is complied with.
(5) No portion of either earth connexion shall be placed within 6 feet of any pipe, the property of the Postmaster-General.
(6) Nothing in this regulation shall authorize the connexion of any generator or return to any main for water supply without the consent of the owner of the main.
(7) Where, from the nature of the soil or for other reasons, the electric authority can show to the satisfaction of the Postmaster General that this regulation cannot be complied with without undue expense, the provisions of this regulation shall not apply.
(
a ) so separate the uninsulated return from the general mass of earth, and from any pipe in the vicinity;(
b ) so connect together the several lengths of the rails;(
c ) adopt such means for reducing the difference produced by the current between the potential of the uninsulated return at any one point and the potential of the uninsulated return at any other point; and(d) so maintain the efficiency of the earth connexions specified in the preceding regulations, as to fulfil the following conditions, viz.:—
(i) That the current passing from the earth connexions through the indicator to the generator, or through the resistance to the insulated return, shall not, at any time exceed either 2 amperes per mile, of single tramway line, or 5 per cent. of the total current output of the station.
(ii) That if at any time and at any place a test be made by connecting a galvanometer or other current indicator between the uninsulated return and any pipe, wire, or work in the vicinity the property of the Postmaster-General, it shall always be possible to reverse the direction of any current indicated by interposing a battery of three Leclanche cells, connected in series if the direction of the current is from the return to the pipe, or by interposing a Leclanche cell if the direction of the current is from the pipe to the return.
(iii) That if at any time it can be shown that within a distance of 1 mile from any part of the tramway system there is a current flowing between any pipe, wire, or work of the Postmaster-General, and any other pipe or metallic substance connected to earth and in close proximity to such pipe, wire, or work of the Postmaster-General, and that such current is due to the operation of the tramway system, it shall be possible to reverse the direction of such current by the insertion of one Leclanche cell.
(2) In order to provide an indication that the condition (i) is complied with, the circuit of the current indicator provided for in regulation 11 shall be closed twice per day for periods of five minutes each at intervals of not less than six hours, and as nearly as possible to the times of maximum output. The maximum reading through the current indicator during each of such tests shall be recorded, together with the output at the time such reading was taken.
(2) In order to provide an indication that the above condition is complied with, a record of such difference of potential and of the output at the time of such observation shall be taken upon each route twice per day for periods of five minutes each at intervals of not less than six hours, and as nearly as possible to the times of maximum output.
(
a ) Where not more than ten telegraph wires cross from one side of the tramway to the other side, and(
b ) Where any number of distributing telegraph wires cross, from a distributing pole, from one side of the tramway to the other side, and(
c ) Where at places other than crossings any bare telegraph wires are liable to fall upon the conductors or other electric wires of the tramway.
(
a ) Where there is one trolley wire two guard wires shall be erected as in Fig. 1.
FIG 1.
(
Fig. 2.
C.19182.—2
(2) Where guard wires are required to be erected for the protection of telegraph wires weighing 100 lbs. or more per mile, they shall be erected as follows:—
(
a ) Where there is only one trolley wire, two guard wires shall be erected as in Fig. 3.Fig. 3.
(
b )Where there are two trolley wires not more than 15 inches apart, two guard wires shall be erected as in Fig. 4.Fig. 4.
(
c )Where there are two trolley wires, and the distance between them exceeds 15 inches, but does not exceed 10 feet, three guard wires shall be erected as in Fig. 5.
Fig. 5.
(
d )Where the distance between the two trolley wires exceeds 10 feet, each trolley shall be separately guarded as in Fig. 6.
Fig. 6.
(3) Subject to the following paragraphs, guard wires shall be so fixed as to be parallel with the trolley wire for a distance on each side of the point where the telegraph wires cross the trolley wire equal to at least twice the perpendicular distance between the highest telegraph wire and the guard wire:—
(a) Where telegraph wires not crossing a trolley wire are liable to fall upon or to be blown on to a trolley wire, or other tramway wire which may become charged to a dangerous potential, the guard wires shall be so erected that a falling telegraph wire must fall on a guard wire before it can fall on the trolley wire or tramway wire.
(
b ) In special cases at junctions or curves where parallel guard wiring would be complicated, guard wires shall be so erected that a falling wire must fall on a guard wire before it can fall on the trolley wire.
(4) Guard wires shall be of galvanized steel, but in places where galvanized steel wires are liable to corrosion, they shall be of bronze or hard-drawn copper, and they shall be of a gauge of not less than seven strands of No. 16, or one of No. 8 wire (S.W.G.).
(5) Guard wires shall be fixed between the trolley wire and the telegraph wires at such a height that the trolley boom of an electric car cannot come into contact with them. They shall be fixed to supports which are rigid, and sufficiently strong for their purpose, and at each support each guard wire shall be securely bound in or terminated.
(6) Guard wires shall be well earthed at one point at least, and at intervals of not more than five spans. The earth connexion shall be made by connecting the wire through the support to the rails by means of a copper bond.
(
a ) Maximum working current.(
b ) Maximum working pressure.(
c ) Maximum current from the earth connexions.(
d ) Leakage current.(
e ) Fall of potential in return.(
f ) Condition of earth connexions.(
g ) Insulation resistance of insulated cables.(
h ) Conductance of joints to pipes.(
h ) Efficiency of guard wire earth connexions.(
j ) Any tests made under provisions of regulation 12 (1) (ii).(
k ) Localization and removal of leakage stating time occupied.(
l )Particulars of any abnormal occurrence affecting the electric working of the tramway.
Part III.—Electric Light and Power Works and Lines.
(
a ) the earth shall not be used as any part of a return circuit; and(
b ) onconnexion with earth, other than one connexion at each generating or transforming station, shall be allowed, with continuous current circuits.
(2) Each earth connexion allowed under this regulation shall be capable of being removed for testing purposes.
(2) Where it is not practicable for the low pressure aerial lines to pass over or under the telegraph lines, then the Postmaster-General or officer authorized by him may grant permission for the low pressure aerial lines to pass between the telegraph lines.
(3) Under-crossings are permissible when no telegraph pole is in such a position as to be between the Electric Authority’s proposed service line, and an imaginary line commencing at the electric authority’s pole, and making an angle of 15 degrees with the proposed service line, provided always such under-crossing does not limit the reasonably anticipated development of the telegraph lines.
(4) When for the purpose of crossing with low pressure aerial lines over or through the telegraph line, the electric authority desires to make an attachment to the telegraph poles, permission for such crossings must be obtained from the Postmaster-General, or officer authorized by him, before the work is commenced.
(5) The attachments must be made in one of the following ways, and in a manner satisfactory to the Postmaster-General:—
(
a ) by the attachment of a crossarm to the Department’s pole;(
b ) by the attachment of a crossarm to an extension of the Department’s pole;(
c ) by the use of insulated wires properly enclosed in an earthed conduit attached to the Department’s poles.
(2)Where the separation between the routes of the lines of an electric authority and those of the Postmaster-General, is less than 1 chain, and where the lines of such electric authority cross a street or road, and cross one or more telegraph lines, the following rules shall apply:—
(
a )Underneath crossings, when permitted, shall be made so that the angle between the low pressure line and the telegraph line at the point of crossing shall be not less than 45 degrees.(
b )Over-crossings shall be made so that the angle between the power lines and the telegraph line at the point of crossing shall be not less than 30 degrees.
(2) Adequate precautions shall be taken to insure that no accumulation of water shall take place in any part of the conduit, and to prevent any dangerous access of moisture to the conductors or the insulators.
(3) In the case of electric lines laid in conduits, the insulators shall be so disposed that they can be readily inspected.
Part IV.—Miscellaneous.
(2) The Postmaster-General shall also bear the cost of all works for the protection of any aerial telegraph line erected by him subsequent to the erection of the line or work against which the protection is required.
(3) The cost of providing metallic circuits or common return wires for telephone lines of the Postmaster-General shall be borne by the Postmaster-General.
Provided, however, that the electric authority shall not be required to pay the cost of any work undertaken by the Postmaster-General if the work was not primarily required for the protection of the telegraph lines of the Postmaster-General from injurious affection by the works of the electric authority.
Printed and Published for the Government of the Commonwealth of Australia by Albert J. Mullett, Government Printer for the State of Victoria.
0
0
0