Gas Standards (Gas Supply and System Safety) Amendment Regulations 2016 (WA)
| 4532 | GOVERNMENT GAZETTE, WA | 11 October 2016 |
ENERGY
EN301
Gas Standards Act 1972
Gas Standards (Gas Supply and System Safety)
Amendment Regulations 2016
Made by the Governor in Executive Council.
1. Citation
These regulations are the Gas Standards (Gas Supply and
System Safety) Amendment Regulations 2016.2. Commencement
These regulations come into operation as follows —
(a) regulations 1 and 2 — on the day on which these regulations are published in the Gazette; (b) the rest of the regulations — on the day after that day. 3. Regulations amended
These regulations amend the Gas Standards (Gas Supply and
System Safety) Regulations 2000.4. Regulation 5 amended
In regulation 5(2)(a) delete “4564-2005:” and insert:
4564-2011
Note: The heading to amended regulation 5 is to read:
Undertakers’ duties as to quality of gas supplied to consumers
5. Regulation 7 amended
(1) In regulation 7(1A):
(a) in paragraph (b) delete “odorising.” and insert: odorising; and
(b) after paragraph (b) insert:
(c) does not include any other substance that — (i) may adversely affect pipework or any other component used to convey the LPG; or
11 October 2016 GOVERNMENT GAZETTE, WA 4533 (ii) may adversely affect any gas appliance in which the LPG is used; or
(iii) may be toxic to a person who has contact with it, or its combustion products, in the course of the normal
operation of any gas appliance in which
the LPG is used.
(2) In regulation 7(1):
(a) in paragraph (b) delete “odorising.” and insert: odorising; and
(b) after paragraph (b) insert:
(c) does not include any other substance that — (i) may adversely affect pipework or any other component used to convey the LPG; or
(ii) may adversely affect any gas appliance in which the LPG is used; or
(iii) may be toxic to a person who has contact with it, or its combustion products, in the course of the normal
operation of any gas appliance in which
the LPG is used.
Note: The heading to amended regulation 7 is to read:
Undertakers’ duties as to quality of LPG supplied to consumers
6. Regulation 12 replaced
Delete regulation 12 and insert:
12. Undertakers’ duties as to supplying mixed LPG for propulsion purposes
An undertaker must ensure that mixed LPG supplied to
a consumer in liquid form for use as a fuel for use in
the propulsion of a vehicle —
(a) is a mixture of — (i) propane or propene, or propane and propene; and
(ii) butanes or butenes, or butanes and butenes;
and
| 4534 | GOVERNMENT GAZETTE, WA | 11 October 2016 |
(b) is supplied at a vapour pressure not exceeding 1 530 kPa (gauge) at 40°C; and (c) does not include any other substance that — (i) may adversely affect pipework or any other component used to convey the mixed LPG; or
(ii) may adversely affect any gas appliance in a vehicle in which the mixed LPG is used; or
(iii) may be toxic to a person who has contact with it, or its combustion products, in the course of the normal operation of any gas appliance in a vehicle in which the mixed LPG is used.
7. Regulation 13 amended
In regulation 13(1):
(a) delete paragraph (a) and insert:
(a) it is supplied as — (i) propane; or
(ii) a mixture of propane and not more than 15 mol% propene;
and
(b) in paragraph (d) delete “odorising.” and insert: odorising; and
(c) after paragraph (d) insert:
(e) it does not include any other substance that — (i) may adversely affect pipework or any other component used to convey the LPG; or
(ii) may adversely affect any gas appliance in which the LPG is used; or
(iii) may be toxic to a person who has contact with it, or its combustion products, in the course of the normal operation of any gas appliance in which the LPG is used.
Note: The heading to amended regulation 13 is to read:
Undertakers’ duties as to supplying LPG through distribution
system
11 October 2016 GOVERNMENT GAZETTE, WA 4535 8. Regulation 15 amended
(1) In regulation 15(1) delete “6 m3 per hour” and insert: 7.5 m3 per hour in air (2) In regulation 15(3):
(a) in paragraph (a) delete “6 m3 per hour; or” and insert: 7.5 m3 per hour in air; or
(b) in paragraph (b) delete “6 m3 per hour.” and insert: 7.5 m3 per hour in air.
Note: The heading to amended regulation 15 is to read:
Operating requirements for master meters
9. Regulation 16 amended
In regulation 16:
(a) in paragraph (c) delete “12 m3 per hour; and” and insert: 12 m3 per hour in air; and
(b) in paragraph (d) delete “6 m3 per hour but not more than 12 m3 per hour; and” and insert: 7.5 m3 per hour in air but not more than 12 m3 per hour
in air; and(c) in paragraph (e) delete “6 m3 per hour,” and insert: 7.5 m3 per hour in air,
Note: The heading to amended regulation 16 is to read:
Replacement of master meters
10. Regulation 43 amended
Delete regulation 43(1)(c)(ii) and insert:
(ii) at least 100 other consumers, in the case of natural gas, and at least 50 other consumers, in the case of LPG.
| 4536 | GOVERNMENT GAZETTE, WA | 11 October 2016 |
11. Schedule 1 replaced
Delete Schedule 1 and insert:
Schedule 1 — Odorant levels for various gases,
vapours and types of odorant
[r. 6(c) and 9(c)]
Odorant type Application Minimum Minimum Maximum TBM total total (mg/m3) (mg/m3) (mg/m3) Mainly tertiary Natural gas: 4 5 15 butyl industrial mercaptan
(TBM)Mainly tertiary Natural gas: 6 8 30 butyl general mercaptan
(TBM)Mainly tetra Natural gas: 3 8 20 hydro industrial thiophene
(THT)Mainly tetra Natural gas: 4 12 30 hydro general thiophene
(THT)Ethyl Liquefied Not 25 100
mercaptan petroleum gas: applicable reticulated
Ethyl Liquefied Not 10 Not
mercaptan petroleum gas applicable applicable (vapour): in a commercially filled cylinder
R. KENNEDY, Clerk of the Executive Council.
———————————