Electricity (General) Variation Regulations 2004 (SA)

Case

South Australia

Electricity (General) Variation Regulations 2004

under the Electricity Act 1996

Contents

Part 1—Preliminary

  1. Short title

  2. Commencement

  3. Variation provisions

Part 2—Variation of Electricity (General) Regulations 1997

  1. Variation of regulation 4—Interpretation

  2. Insertion of regulation 5AC

    5ACCompliance with standards that are varied or substituted

  3. Variation of regulation 6—Exemptions from requirement to be licensed

  4. Variation of regulation 17—Electrical installations

  5. Variation of regulation 18—Certain electrical installation work and certificates of compliance

  6. Substitution of heading to Part 4 Division 5

  7. Variation of regulations 31C—Safety, reliability, maintenance and technical management plans

  8. Variation of regulation 31D—Safety, reliability, maintenance and technical management reports

  9. Variation of regulation 39—Erection of buildings in proximity to aerial lines

  10. Variation of Schedule 2—Requirements for aerial lines

  11. Variation of Schedule 3—Requirements for underground lines and certain other powerlines

  12. Variation of Schedule 4—Requirements for substations

  13. Variation of Schedule 5—Requirements for earthing and electrical protection systems

Part 1—Preliminary

1—Short title

These regulations may be cited as the Electricity (General) Variation Regulations 2004.

2—Commencement

These regulations come into operation on the day on which they are made.

3—Variation provisions

In these regulations, a provision under a heading referring to the variation of specified regulations varies the regulations so specified.

Part 2—Variation of Electricity (General) Regulations 1997

4—Variation of regulation 4—Interpretation

  1. Regulation 4(1), definition of AS or Australian Standard—delete the definition and substitute:

    AS or Australian Standard, followed by a number, or AS/NZS or Australian/New Zealand Standard followed by a number, is a reference to the standard published by Standards Australia as in force from time to time;

    centre-line, in relation to an aerial line, means a notional vertical plane extending upwards from any point on the ground and running through, and connecting, the centre of each structure that supports the aerial line;

  2. Regulation 4(1)—after the definition of connection point insert:

    facade mounted line means an aerial line attached to a building;

  3. Regulation 4(1), definition of low voltage or LV—delete "AS" and substitute:

    AS/NZS

  4. Regulation 4(1), definition of multiple earthed neutral system or MEN system—delete "AS" and substitute:

    AS/NZS

  5. Regulation 4(2)—delete subregulation (2)

  6. Regulation 4(4)—delete "subregulations (2) and (3)" and substitute:

    subregulation (3)

5—Insertion of regulation 5AC

After regulation 5AB insert:

5AC—Compliance with standards that are varied or substituted

(1)Despite a requirement of these regulations for work to be carried out in accordance with a standard as in force from time to time, where the standard is varied or substituted, work for the installation, commissioning or modification of electricity infrastructure or an electrical installation may be carried out in accordance with the old standard—

(a)if—

(i)design work for that installation, commissioning or modification had been completed before (but not more than 1 month before) the publication of the new standard; or

(ii)the work (disregarding design or other preparatory work) had commenced before the publication of the new standard; or

(iii)the work commenced after the publication of the new standard and is to be completed within 6 months after that publication; or

(iv)the work is connected with the construction of premises and construction work had commenced before the publication of the new standard; or

(b)in any other case—with the approval of the Technical Regulator, on terms and conditions the Technical Regulator considers appropriate.

(2)If—

(a)pursuant to subregulation (1) work is purportedly carried out in accordance with an old standard; and

(b)the work complies with that old standard,

an approval or certification that the work complies with the standard may be given for the purposes of these regulations.

(3)In this regulation—

(a)a reference to a standard includes a reference to—

(i)a code, guide or other document; and

(ii)a part of a standard, code, guide or other document; and

(b)a standard as in force following the variation or substitution of the standard is referred to as the new standard; and

(c)a standard as in force immediately prior to the variation or substitution of the standard is referred to as the old standard; and

(d)a reference to work includes a reference to examinations and tests related to the work.

(4)This regulation does not apply in relation to the National Electricity Code or a code made by the Commission under the Essential Services Commission Act 2002.

6—Variation of regulation 6—Exemptions from requirement to be licensed

Regulation 6(6)—delete subregulation (6) and substitute:

(6)An exemption from subregulation (5), or from specified requirements referred to in that subregulation, may be granted by—

(a)in relation to Part 6 of the Act or Parts 4, 5 and 6 of these regulations or any safety requirement—the Technical Regulator, on terms and conditions the Technical Regulator considers appropriate; or

(b)in any other case—the Commission, on terms and conditions the Commission considers appropriate.

7—Variation of regulation 17—Electrical installations

  1. Regulation 17—delete "AS" wherever occurring and substitute in each case:

    AS/NZS

  2. Regulation 17—after "Australian Standard" insert:

    or Australian/New Zealand Standard

  3. Regulation 17—after its present contents as amended by this regulation (now to be designated as subregulation (1)) insert:

    (2)Despite any other regulation—

    (a)aerial lines, underground lines or other powerlines; and

    (b)earthing and electrical protection systems,

    that form part of an electrical installation and that comply with AS/NZS 3000 and any other Australian Standard or Australian/New Zealand Standard called up by AS/NZS 3000, will be taken to comply with these regulations.

8—Variation of regulation 18—Certain electrical installation work and certificates of compliance

  1. Regulation 18(1)(a)—delete "AS" wherever occurring and substitute in each case:

    AS/NZS

  2. Regulation 18(1)(a)—after "Australian Standard" wherever occurring insert in each case:

    or Australian/New Zealand Standard

9—Substitution of heading to Part 4 Division 5

Heading to Part 4 Division 5—delete the heading and substitute:

Division 5—Safety, reliability, maintenance and technical management plans and reports

10—Variation of regulations 31C—Safety, reliability, maintenance and technical management plans

Regulation 31C—delete "safety and technical management plan" wherever occurring and substitute in each case:

safety, reliability, maintenance and technical management plan

11—Variation of regulation 31D—Safety, reliability, maintenance and technical management reports

  1. Regulation 31D(2)—delete "Subclause" and substitute:

    Subregulation

  2. Regulation 31D(3)(c)—delete "safety and technical management plan" and substitute:

    safety, reliability, maintenance and technical management plan

  3. Regulation 31D—after subregulation (3) insert:

    (4)However, this regulation only applies to a person who is exempted from the requirement to hold a licence to the extent specified by the Technical Regulator by notice in writing to the person.

12—Variation of regulation 39—Erection of buildings in proximity to aerial lines

  1. Regulation 39(1)—delete subregulation (1) and substitute:

    (1)For the purposes of section 86 of the Act, a person must not, except as approved by the Technical Regulator, erect a building or structure in proximity to an aerial line as follows:

    (a)in the case of an aerial line (other than a facade mounted line) constructed to operate at a voltage of more than 33kV—

    (i)under the aerial line; or

    (ii)so that the horizontal distance from any part of the building or structure to the centre-line of any such aerial line is less than the relevant distance as set out in Table 1 in Schedule 2;

    (b)in the case of an aerial line (other than a facade mounted line) or other cable system constructed to operate at a voltage of 33kV or less—so that the vertical or horizontal distance from any part of the building or structure to any position to which a conductor in the aerial line or other cable system may sag at maximum design temperature, or move as a result of normal prevailing wind pressures, is less than the relevant distance as set out in Table 1 in Schedule 2.

    Note—

    The figures following Table 1 are to be used to assist in understanding the information contained in the Table.

  2. Regulation 39(1a)—delete "subregulation (1)(b)" and substitute:

    subregulation (1)

13—Variation of Schedule 2—Requirements for aerial lines

  1. Schedule 2, clause 10(4)(a) to (c)—delete paragraphs (a) to (c) and substitute:

    (a)for an aerial line (other than a facade mounted line) constructed to operate at a voltage of 33kV or less—so that the vertical or horizontal distance from any building or structure (other than a support to which the aerial line is attached or a support of another overhead line which crosses the aerial line) to any position to which a conductor in the aerial line may sag at maximum design temperature, or move as a result of normal prevailing wind pressures, is not less than the relevant distance as set out in Table 1;

    Note—

    The figures following Table 1 are to be used to assist in understanding the information contained in the Table.

    (ab)for an aerial line (other than a facade mounted line) constructed to operate at a voltage of more than 33kV—so that the horizontal distance from any building or structure (other than a support to which the aerial line is attached or a support of another overhead line which crosses the aerial line) to the centre-line of the aerial line is not less than the relevant distance as set out in Table 1;

    Note—

    The figures following Table 1 are to be used to assist in understanding the information contained in the Table.

    (b)for an aerial line (other than a service line, other cable system or aerial line within a substation)—so that the distance to the ground in any direction from a position to which any part of the aerial line may sag at maximum design temperature, or move as a result of normal prevailing wind pressures, is not less than the relevant distance as set out in Table 2;

    (c)for a service line or other cable system—so that the distance to the ground in any direction from a position to which any part of the service line or cable system may sag at maximum design temperature, or move as a result of normal prevailing wind pressures, is not less than the relevant distance as set out in Table 3;

  2. Schedule 2, clause 13, table 1—delete "from centre of pole" and substitute:

    from centre-line of aerial line

  3. Schedule 2, clause 13, table 1—delete "In any other direction" and substitute:

    Horizontally

  4. Schedule 2, clause 13, table 1—delete "In any direction" first occurring and substitute:

    Horizontally

  5. Schedule 2, clause 13, table 1—delete "(G)"

  6. Schedule 2, clause 13, figure 1 (following table 1)—delete everything relating to figure 1 and substitute:

    Table 1 figures—

    1Figures (a) and (b) will assist in understanding the required minimum safety clearance for aerial lines constructed to operate at a voltage of more than 33kV.

    2Figure (c) will assist in understanding the required minimum safety clearance for aerial lines constructed to operate at a voltage of 33kV or less (that is, minimum safety clearance from nearest conductor (maximum swing and sag)).

    (a)

    (b)

    (c)

  7. Schedule 2, clause 13, heading to figure 2—delete the heading to figure 2 and substitute:

    Table 4 figures—

  8. Schedule 2, clause 13, figure 2—delete "Figure 2 is to be used" and substitute:

    The following figures will assist

  9. Schedule 2, appendix—delete the appendix and substitute:

    Appendix—Standards, codes, guides and other documents relating to aerial lines

In this Appendix—

ESAA means Electricity Supply Association of Australia.

Conductors

Conductor - Bare overhead - Hard - drawn copper................................................................................................................

AS 1746

Conductor - Bare overhead - Aluminium and aluminium alloy................................................................................................................

AS 1531

Conductor - Bare overhead, aluminium and aluminium alloy - Steel reinforced................................................................................................................

AS 3607

Steel conductors and stays - Bare overhead - Galvanised (SC/GZ)................................................................................................................

AS 1222

Steel conductors and stays - Bare overhead - Aluminium clad (SC/AC)................................................................................................................

AS 1222

Galvanised steel wire strand................................................................................................................

AS 2841

Insulated cables

Electric cables - Polymeric insulated - For working voltages up to and including 0.6/1(1.2)kV................................................................................................................

AS/NZS 5000

Electric cables - Polymeric insulated - For distribution and service applications................................................................................................................

AS/NZS 4961

Electric cables - Cross-linked polyethylene insulated - Aerial bundled - For working voltages up to and including 0.6/1(1.2)kV................................................................................................................

AS/NZS 3560

Mechanical fittings for low voltage aerial bundled cable................................................................................................................

AS 3766

Electric cables - Aerial bundled - Polymeric insulated - Voltages 6.35/11(12)kV and 12.7/22(24)kV - Metallic screened................................................................................................................

AS/NZS 3599

Electric cables - Aerial bundled - Polymeric insulated - Voltages 6.35/11(12)kV and 12.7/22(24)kV - Non-metallic screened................................................................................................................

AS/NZS 3599

Conductors - Covered overhead - For working voltages 6.35/11(12)kV up to and including 19/33(36)kV................................................................................................................

AS/NZS 3675

Insulators

Insulators - Ceramic or glass - Station post for indoor and outdoor use - Voltages greater than 1000V ac................................................................................................................

AS 4398

Insulators - Porcelain and glass for overhead powerlines - Voltages greater than 1000V ac - Test methods - Insulator units................................................................................................................

AS/NZS 2947

Insulators - Porcelain and glass for overhead powerlines - Voltages greater than 1000V ac................................................................................................................

AS/NZS 2947

Insulators - Porcelain and glass for overhead powerlines - Voltages greater than 1000V ac - Couplings................................................................................................................

AS 2947

Insulators - Porcelain and glass for overhead powerlines - Voltages greater than 1000V ac - Test methods - Insulator strings and insulator sets................................................................................................................

AS/NZS 2947

Insulators - Porcelain and glass, pin and shackle type - Voltages not exceeding 1000V ac................................................................................................................

AS 3608

Insulators - Porcelain stay type - Voltages greater than 1000V ac................................................................................................................

AS 3609

Guidelines for the design and maintenance of overhead distribution and transmission lines—

Selection........................................................................................................

ESAA C(b)1

Insulator and conductor fittings

Insulator and conductor fittings for overhead powerlines - Performance, material, general requirements and dimensions................................................................................................................

AS 1154

Insulator and conductor fittings for overhead powerlines - Performance and general requirements for helical fittings................................................................................................................

AS 1154

Thermal limits

Guidelines for the design and maintenance of overhead distribution and transmission lines—

Thermal limits........................................................................................................

ESAA C(b)1

Current rating of bare overhead line conductors................................................................................................................

ESAA D(b)5

Short circuit capacity

Guidelines for the design and maintenance of overhead distribution and transmission lines—

Fault ratings........................................................................................................

ESAA C(b)1

Mechanical loading conditions

Guidelines for the design and maintenance of overhead distribution and transmission lines—

Mechanical loading conditions........................................................................................................

ESAA C(b)1

Structural design actions - General principles................................................................................................................

AS/NZS 1170

Structural design actions - Permanent, imposed and other actions................................................................................................................

AS/NZS 1170

Structural design actions - Wind actions................................................................................................................

AS/NZS 1170

Minimum design loads on structures (known as the SAA Loading Code) - Earthquake loads................................................................................................................

AS 1170

Conductor tensions

Guidelines for the design and maintenance of overhead distribution and transmission lines—

General........................................................................................................

ESAA C(b)1

Calculations........................................................................................................

ESAA C(b)1

Structures and footings

Guidelines for the design and maintenance of overhead distribution and transmission lines—

General........................................................................................................

ESAA C(b)1

Methods of testing soils for engineering purposes................................................................................................................

AS 1289 Series

Piling - Design and installation................................................................................................................

AS 2159

Design of steel lattice towers and masts................................................................................................................

AS 3995

Steel structures................................................................................................................

AS 4100

Concrete structures................................................................................................................

AS 3600

Clearances from ground

Guidelines for the design and maintenance of overhead distribution and transmission lines—

Environmental and loading conditions........................................................................................................

ESAA C(b)1

Clearances from structures

Guidelines for the design and maintenance of overhead distribution and transmission lines—

Environmental and loading conditions........................................................................................................

ESAA C(b)1

Spacing of conductors

Guidelines for the design and maintenance of overhead distribution and transmission lines—

Clearances........................................................................................................

ESAA C(b)1

Environmental and loading conditions........................................................................................................

ESAA C(b)1

Maintenance

Guidelines for the design and maintenance of overhead distribution and transmission lines—

Maintenance and inspection procedures........................................................................................................

ESAA C(b)1

14—Variation of Schedule 3—Requirements for underground lines and certain other powerlines

  1. Schedule 3, clause 2—delete paragraph (d) and substitute:

    (d)the required clearances between a building or structure and an underground powerline as prescribed by regulation 39A are maintained,

  2. Schedule 3, clause 7(2)(a)—delete "AS 1480" and substitute:

    AS 3600

  3. Schedule 3, clause 7(2)(b)—delete "AS 1480" and substitute:

    AS 3600

  4. Schedule 3, clause 7(3)—delete "AS 2053" and substitute:

    AS/NZS 2053

  5. Schedule 3, clause 8(2)(a)—delete "AS 1650" and substitute:

    AS/NZS 4680, AS/NZS 4791 or AS/NZS 4792

  6. Schedule 3, clause 8(3)(a)—delete "AS 2607" and substitute:

    AS 2067

  7. Schedule 3, appendix—delete the appendix and substitute:

    Appendix—Standards, codes, guides and other documents relating to underground lines

In this Appendix—

ANSI means American National Standards Institute;

ESAA means Electricity Supply Association of Australia;

IEC means International Electrotechnical Commission;

IEEE means Institute of Electrical and Electronic Engineers.

High voltage cables

Electric cables - Polymeric insulated - For working voltages 1.9/3.3(3.6)kV up to and including 19/33(36)kV...........................................................................................................

AS/NZS 1429

Electric cables - Impregnated paper insulated - For working voltages up to and including 19/33(36)kV...........................................................................................................

AS/NZS 1026

Electric cables - For underground residential distribution systems...........................................................................................................

AS/NZS 4026

Power cables with extruded insulation and their accessories for rated voltages from 1kV up to 30kV...........................................................................................................

IEC 60502

Power cables with extruded insulation and their accessories for rated voltages above 30kV up to 150kV - Test methods and requirements...........................................................................................................

IEC 60840

Low voltage cables

Electric cables - Impregnated paper insulated - For working voltages up to and including 19/33(36)kV...........................................................................................................

AS/NZS 1026

Conductors in insulated electric cables and flexible cords...........................................................................................................

AS/NZS 1125

Electric cables - Polymeric insulated - For distribution and service applications...........................................................................................................

AS/NZS 4961

Electric cables - Polymeric insulated - For working voltages up to and including 0.6/1(1.2)kV...........................................................................................................

AS/NZS 5000

Electric cables - For underground residential distribution systems...........................................................................................................

AS/NZS 4026

High voltage cable accessories

High Voltage Cable Terminations...........................................................................................................

ANSI/IEEE 48

High Voltage Cable Joints...........................................................................................................

ANSI/IEEE 404

Separable insulated connectors for power distribution systems above 1kV...........................................................................................................

AS 2629

Continuous cable ratings

Electric cables - Calculation of the current rating...........................................................................................................

IEC 60287

Electrical installations - Selection of cables - Cables for alternating voltages up to and including 0.6/1kV...........................................................................................................

AS/NZS 3008

Short circuit currents

Calculation of short circuit currents...........................................................................................................

IEC 60949

Installation

ESAA Guide to the Installation of Cables Underground...........................................................................................................

C(b)2

ESAA Guide to the Use of Separable Connectors...........................................................................................................

D(b)30

Services in Streets—A Code for the Placement of Infrastructure Services in New and Existing Streets (prepared for PUACC and published September 1997)

Maintenance

ESAA Guide for the Maintenance of High Voltage Paper/Oil Insulated Cables and Accessories...........................................................................................................

D(b)31

15—Variation of Schedule 4—Requirements for substations

  1. Schedule 4, clause 8(4)—after "barbed wire" insert:

    , or razor wire,

  2. Schedule 4, clause 8(4)—after "0.15 m" insert:

    or tiger tape flat loops

  3. Schedule 4, appendix—delete the appendix and substitute:

    APPENDIX—Standards, codes, guides and other documents relating to substations

In this Appendix—

ESAA means Electricity Supply Association of Australia;

IEC means International Electrotechnical Commission;

IP Code means International Protection Code.

Electrical design

Switchgear assemblies & ancillary equipment for alternating voltages above 1kV................................................................................................................

AS 2067

Circuit breakers and ancillary equipment

Degrees of protection provided by enclosures (IP Code)................................................................................................................

AS 60529

High voltage ac switchgear and controlgear - Circuit breakers for rated voltages above 1000 V................................................................................................................

AS 2006

Switchgear assemblies and ancillary equipment

High voltage switches - Switches for rated voltages above 1kV and less than 52kV................................................................................................................

AS/NZS 60265

High voltage, ac switchgear and controlgear - Switches and switch-disconnectors - For rated voltages of 52kV and above................................................................................................................

AS 1025

High voltage ac switchgear and controlgear - Disconnectors (isolators) and earthing switches................................................................................................................

AS 1306

High voltage ac switchgear and controlgear - Switch-fuse combinations................................................................................................................

AS 2024

Common specifications for high-voltage switchgear and controlgear standards................................................................................................................

AS/NZS 2650

AC metal-enclosed switchgear and controlgear for rated voltages above 1kV and up to and including 72.5kV................................................................................................................

AS 2086

AC insulation-enclosed switchgear and controlgear for rated voltages above 1kV and up to and including 38kV................................................................................................................

AS 2264

Switchgear assemblies and ancillary equipment for alternating voltages above 1 kV................................................................................................................

AS 2067

Degrees of protection provided by enclosures (IP Code)................................................................................................................

AS 60529

Insulating liquids - Specifications for unused mineral insulating oils for transformers and switchgear................................................................................................................

AS 1767

Control equipment

Low-voltage switchgear and controlgear -General rules................................................................................................................

AS 60947

Low-voltage switchgear and controlgear -Switches, disconnectors, switch-disconnectors and fuse combination units................................................................................................................

AS/NZS 3947

Low-voltage switchgear and controlgear -Contactors and motor starters: Electromechanical contactors and motor starters................................................................................................................

AS 60947

Low-voltage switchgear and controlgear -Circuit control devices and switching elements - Electromechanical control circuit devices................................................................................................................

AS 60947

Low-voltage switchgear and controlgear -Control circuit devices and switching elements - Proximity switches................................................................................................................

AS 60947

Insulating panels

Sheets and boards for electrical purposes - Classification and general requirements................................................................................................................

AS 1795

Sheets and boards for electrical purposes -Dimensions of switchboard panels................................................................................................................

AS 1795

Power transformers

Power transformers - General................................................................................................................

AS 2374

Power transformers - Temperature rise................................................................................................................

AS 2374

Power transformers - Insulation levels and dielectric tests - General requirements................................................................................................................

AS 2374

Power transformers - Insulation levels and dialectric tests - External clearances in air................................................................................................................

AS 2374

Power transformers - Ability to withstand short circuit................................................................................................................

AS 2374

Power transformers - Determination of transformer and reactor sound levels................................................................................................................

AS 2374

Insulating liquids - Specification for unused mineral insulating oils for transformers and switchgear................................................................................................................

AS 1767

Bushings

Bushings for alternating voltages above 1000 V................................................................................................................

AS 1265

Surge arresters

Surge arresters (diverters) - Silicon carbide type for ac systems................................................................................................................

AS 1307

Surge arresters - Metal-oxide surge arresters without gaps for ac systems................................................................................................................

AS 1307

Batteries

Stationary batteries - Lead-acid - Vented type................................................................................................................

AS 4029

Stationary batteries - Lead-acid - Valve-regulated type................................................................................................................

AS/NZS 4029

Stationary batteries - Lead-acid - Pure lead positive pasted plate type................................................................................................................

AS 4029

Insulation coordination

Insulation coordination - Definitions, principles and rules................................................................................................................

AS 1824

Insulation coordination (phase-to-earth and phase-to-phase, above 1 kV) - Application Guide................................................................................................................

AS 1824

Insulation coordination for equipment within Low Voltage systems: Principles, requirements and tests................................................................................................................

IEC 60664

Safety clearances

Degrees of protection provided by enclosures (IP Code)................................................................................................................

AS 60529

Switchgear assemblies and ancillary equipment for alternating voltages above 1kV................................................................................................................

AS 2067

Buildings and enclosures

Building Code of Australia

Fixed platforms, walkways, stairways and ladders: Design construction and installation................................................................................................................

AS 1657

The use of ventilation and air conditioning in buildings -Ventilation design for indoor air contaminant control................................................................................................................

AS 1668

The use of ventilation and air conditioning in buildings - Fire and smoke control in multi-compartment buildings................................................................................................................

AS/NZS 1668

Degrees of protection provided by enclosures (IP Code)................................................................................................................

AS 60529

The storage and handling of flammable and combustible liquids................................................................................................................

AS 1940

Oil containment................................................................................................................

Environment Protection Authority

Electrical installations - Secondary batteries installed in buildings - Vented cells................................................................................................................

AS 3011

Electrical installations -Secondary batteries installed in buildings - Sealed cells................................................................................................................

AS 3011

Switchyard structures, footings and foundations

Structural design actions - General principles................................................................................................................

AS/NZS 1170

Structural design actions - Permanent, imposed and other actions................................................................................................................

AS/NZS 1170

Structural design actions - Wind actions................................................................................................................

AS/NZS 1170

Minimum design loads on structures (known as the SAA Loading Code) - Earthquake loads................................................................................................................

AS 1170

Design of steel lattice towers and masts................................................................................................................

AS 3995

Steel structures................................................................................................................

AS 4100

Concrete structures................................................................................................................

AS 3600

Maintenance

Guide to maintenance and supervision of insulating oils in service................................................................................................................

AS 1883

Maintenance of electrical switchgear................................................................................................................

AS 2467

Guide to the installation, maintenance, testing and replacement of secondary batteries in buildings - Vented cells................................................................................................................

AS 2676

Guide to the installation, maintenance, testing and replacement of secondary batteries in buildings - Sealed Cells................................................................................................................

AS 2676

16—Variation of Schedule 5—Requirements for earthing and electrical protection systems

  1. Schedule 5, clause 5—delete "AS" wherever occurring and substitute in each case:

    AS/NZS

  2. Schedule 5, clause 8—delete "of Clause 12"

  3. Schedule 5, appendix—delete the appendix and substitute:

    Appendix—Standards, codes, guides and other documents relating to earthing and electrical protection systems

In this Appendix—

ESAA means Electricity Supply Association of Australia;

IEEE means Institute of Electrical and Electronic Engineers.

Protection

All or nothing relays................................................................................................................

AS 2481

Voltage transformers for measurement and protection................................................................................................................

AS 1243

Current transformers for measurement and protection................................................................................................................

AS 1675

Low voltage switchgear and controlgear - General rules................................................................................................................

AS 60947

Low voltage switchgear and controlgear - Switches, disconnectors, switch-disconnectors and fuse-combination units................................................................................................................

AS/NZS 3947

Low voltage switchgear and controlgear - Contactors and motor starters - Electromechanical contactors and motor starters................................................................................................................

AS 60947

Low voltage switchgear and controlgear - Control circuit devices and switching elements - Electromechanical control circuit devices................................................................................................................

AS 60947

Low voltage switchgear and controlgear - Control circuit devices and switching elements - Proximity switches................................................................................................................

AS 60947

Earthing

Switchgear assemblies and ancillary equipment for alternating voltages above 1kV................................................................................................................

AS 2067

Guide for safety in AC substation grounding................................................................................................................

IEEE 80

Electrical installations................................................................................................................

AS/NZS 3000

Relocatable premises (including caravans and tents) and their site installations................................................................................................................

AS/NZS 3001

Guidelines for the design and maintenance of overhead distribution and transmission lines—

Stay wires........................................................................................................

ESAA C(b)1

Step and touch potentials........................................................................................................

ESAA C(b)1

Switchgear assemblies and ancillary equipment for alternating voltages above 1kV................................................................................................................

AS 2067

ESAA - Earth Potential Rise Code of Practice

ESAA - Earth Return High Voltage Power Lines Code of Practice

Maintenance

Switchgear assemblies and ancillary equipment for alternating voltages above 1kV................................................................................................................

AS 2067

Electrical installations................................................................................................................

AS/NZS 3000

Guide to safety in AC substation grounding................................................................................................................

IEEE 80

Guidelines for the design and maintenance of overhead distribution and transmission lines................................................................................................................

ESAA C(b)1

ESAA - Earth Potential Rise Code of Practice

ESAA - Earth Return High Voltage Power Lines Code of Practice

Testing

Electrical installations - Earthing................................................................................................................

AS/NZS 3000

Guide for safety in AC substation grounding................................................................................................................

IEEE 80

ESAA Guidelines for the design and maintenance of overhead distribution and transmission lines................................................................................................................

ESAA C(b)1

Note—

As required by section 10AA(2) of the Subordinate Legislation Act 1978, the Minister has certified that, in the Minister's opinion, it is necessary or appropriate that these regulations come into operation as set out in these regulations.

Made by the Governor

with the advice and consent of the Executive Council

on 16 December 2004

No 252 of 2004

MENE021/04CS